MBtekUNI 60 Docs
3 · Installation

Hydronic piping

Pipe the UNI 60 — 2 in supply and return, mandatory safety relief valve, expansion tank, drain and return-temperature protection to stop condensation corrosion.

Updated

Pipe the boiler with 2 in supply and return, a safety relief valve that can never be isolated, an expansion tank, a drain, and return-temperature protection. The relief valve and the return protection are the two items installers most often defer — and the two that cause the most expensive failures.

Relief valve is mandatory

Never use the appliance without a relief valve. Position the discharge drainage so that it is safe in case of opening — it discharges boiling water under pressure.

Connection schedule

ConnectionSizeNotes
Supply (flow)2 inCallout 11 on the structure drawing
Return2 inCallout 12
DrainCallout 13, at the base
Flue outlet8 inCallout 4
Sensor wellCallout 14, top of the boiler

Required devices

Safety relief valve

Fit it on the boiler side of any isolating valve, so it can never be valved out. Run the discharge to a safe location.

Maximum operating pressure is 15 psi; maximum test pressure is 50 psi; pressure must never be allowed above 36 psi.

Expansion tank

An open or membrane expansion tank is required on both closed and open systems. Size it from the heating volume as part of the system design.

Return-temperature protection

Fit a thermostatic valve that holds the return above roughly 130 °F.

A boiler protection valve is mandatory if the system operates below 140 °F.

If you use direct circulation without a thermostatic valve and the return falls below 122 °F, the supply must be set to at least 149 °F to avoid condensation.

Check valve on make-up

If using automatic make-up water, install a check valve according to local regulations. Fill at a pressure not exceeding the maximum working boiler pressure.

Flow bypass

Include a bypass so the pumps always have a path, even when every zone actuator is closed. The controller forces all pumps on above the boiler cooling temperature.

Why return protection matters

Note from the UNI install guide: the use of a boiler protection valve is a must if using below 140 degrees Fahrenheit, because return water can generate heavy condensation on the unit giving the impression of a water leak
MBtek install-guide note. Condensation from a cold return is routinely mistaken for a leaking boiler. Source: UNI Install Guide, page 1.

Cold return water condenses acidic moisture and tar onto the inside of the firebox and heat exchanger. That does three things, all bad:

  1. It corrodes the steel body from the inside.
  2. It glues soot and tar to the heat transfer surfaces, cutting efficiency.
  3. It pushes more tar into the chimney, increasing sweeping frequency and fire risk.

MBtek sells an all-in-one boiler station — pump, thermostatic valve and thermometer in one insulated assembly — and a standalone thermostatic boiler protection valve for this purpose.

Recommended installation scheme with the boiler station between the boiler and the buffer tank
The boiler station sits on the return, between the boiler and the rest of the system. Source: UNI Boiler Manual §8.1.

Natural circulation layouts

If the system circulates by gravity, place the return water pipe below the radiator. Without that height difference the system will not move water.

Pipe for maintenance

  • Fit isolating valves so the boiler can be drained without emptying the building.
  • Leave the sensor well accessible — the boiler sensor and STB both live there.
  • Keep the front 36 in and one side 16 in clear of pipework so the boiler can be brushed out.
NextFilling and water quality

Water hardness limits, venting, and the pressure test.

On this page