UNI 60 wood boiler documentation
Official MBtek documentation for the UNI 60 (200K BTU) wood gasification boiler — specifications, installation, TIS Tronic 260U controller setup, operation and service.
The MBtek UNI 60 is a 200,000 BTU wood gasification boiler that heats up to 5,000 ft² of hydronic space heating and domestic hot water from split firewood, coal or woodchips. This site is the complete manual: it takes the boiler from the delivery crate through planning, installation, controller setup, first firing, and everything that follows in service.
- Heat output
- 85–205 KBTU
- Heated area
- Up to 5,000 ft²
- Water volume
- 40 gal
- Firebox
- 58 gal
- Max log length
- 26 in
- Weight
- 1,224 lb
- Connections
- 2 in
- Flue outlet
- 8 in
- Controller
- TIS Tronic 260U

How to read this documentation
Read it in order the first time. The sidebar follows the real sequence of a UNI 60 project, and every section ends by pointing at the next one.
1 · Get started
Quick start checklist, how gasification works, full specifications, delivery contents and the safety rules.
2 · Plan the installation
Boiler room clearances, chimney sizing, hydronic scheme, buffer tank, hot water and fuel storage.
3 · Install
Position, pipe, fill, wire the sensors and pumps, mount the controller and commission the boiler.
4 · Set up the controller
TIS Tronic 260U first start, MBtek recommended settings, operating modes, hot water and alarms.
5 · Operate
First firing, loading the firebox, choosing and drying fuel, and end-of-season shutdown.
6 · Maintain and troubleshoot
Cleaning schedule, chimney care, spare parts, alarm codes and a symptom-first fault guide.
Who this is for
This documentation is written for the installer first and the owner second. Some steps are legally and practically restricted:
| Task | Who may do it |
|---|---|
| Heating system design | Qualified hydronic heating professional |
| Boiler and pipework installation | Qualified heating installer |
| Electrical connection | Licensed electrician |
| First firing and commissioning | Trained installer or service technician |
| Daily loading, ash removal, cleaning | The owner, once trained on the unit |
| Warranty repair | MBtek-accredited service centre or distributor |
Commissioning affects your warranty
The warranty card must be filled in with the commissioning date by the qualified installer. A boiler commissioned outside these instructions, or run on an open heating system, can lose warranty cover. See Warranty.
What the UNI 60 is not
It is an indoor, closed-system, solid-fuel boiler — not an outdoor furnace and not a standalone appliance. Planning around those limits early avoids expensive rework:
- It must be installed indoors, with natural or forced draft.
- It must run on a closed heating system with an expansion tank and a safety relief valve. Open systems corrode the body quickly and void the warranty.
- It needs 230 V mains power for the controller and fan. It is not an off-grid boiler; if you need one, look at the non-gasification PRO series on mbtek.com.
- It needs thermal storage or a carefully designed load — a full firebox releases more heat than most buildings need at that moment.
Naming note
In the original factory boiler manual the UNI 60 appears as "UNI 55". The model was renamed for the North American market; the technical data is identical — 85–205 KBTU, 40 gal water volume, 58 gal firebox, 2 in connections, 8 in flue. Where this documentation and the scanned manual disagree, the figures published on the current MBtek specification sheet are authoritative.
NextQuick startThe one-page checklist of every stage, in order.