Parameter reference

Every TIS Tronic 260U parameter in one table — menu location, range, factory default and the MBtek recommended value for the UNI 60.

Updated

Every parameter the TIS Tronic 260U exposes, with its range, factory default and MBtek's value for the UNI 60. Where the MBtek column is blank, the factory default stands.

User menu

ParameterRangeFactory defaultMBtek UNI 60
Fan maximum capacitymin + 1 … 100 %50 %80 %
Fan minimum capacity1 % … max − 1 %10 %40 %
Fan capacity in supervision1 … 100 %25 %35 %
Purge time (fan ON)5 … 60 s10 s10 s
Time between blowups (fan OFF)1 … 20 min5 min5 min

Thermostat menu

ParameterRangeFactory defaultMBtek UNI 60
CH room thermostatOn / offPer installation
CH pump operating time30 … 250 s30 s
CH pump pause time0 … 240 min1 min

HUW menu

ParameterRangeFactory defaultMBtek UNI 60
HUW operating modeOff / Summer / WinterOffPer installation
HUW priorityOn / offPer installation
HUW temperature increase5 … 15 °C5 °C
HUW operating time10 … 240 min30 min
HUW hysteresis1 … 15 °C5 °C

Boiler settings

ParameterRangeFactory defaultMBtek UNI 60
Boiler operating modeStandard / Brager Expert / Brager Expert exhaust gasesStandardBrager Expert exhaust gases
Brager Expert exhaust gases firing-up time0 … 250 min10 min10 min
Fan slowdown threshold3 … 30 °C12 °C12 °C / 21 °F
Boiler hysteresis1 … 3 °C2 °C2 °C / 5 °F
Maximum boiler temperature70 … 90 °C85 °C80 °C / 176 °F
Boiler shutdown temperature30 … 45 °C35 °C35 °C / 95 °F
Pump start temperature35 … 60 °C35 °C35 °C / 95 °F
Fan type07 / DM85 · 06/145 / DM80WPA 07 / DM85
Firing-up time30 … 120 min120 min120 min
Boiler cooling temperature70 … 85 °C78 °C78 °C / 172 °F
Exhaust gases temperature sensorOn / offOffOn (PT1000 required)
Fuel shortage detection methodBoiler sensor / exhaust sensorBoiler sensorPer installation
Exhaust gas temperature, fuel shortage detection threshold30–90 °CPer installation
Fuel shortage detection time2–200 minPer installation
Fuel shortage CH pump OFFYES / NOPer installation
CH pump shutdown delay5–120 minPer installation

Main screen setpoints

SetpointWhereMBtek UNI 60
Boiler temperatureBoiler main screen, UP / DOWN65 °C / 149 °F
Exhaust gas temperatureExhaust main screen (Brager Expert exhaust gases only)160–240 °C / 320–464 °F
HUW temperatureHUW main screen, UP / DOWNPer installation

Informational items

ItemPurpose
Brager ExpertAdvanced options for the Brager Expert algorithm
Software versionThe installed controller software version
Reset to default settingsReturn to factory defaults
Language selectionInterface language

Device parameters

PropertyValue
Power230 V / 50 Hz AC
Relative humidity30 … 75 %
Ambient temperature5 … 40 °C
Fan output Q11 A
Central pump output Q31 A
HUW pump output Q41 A
Power consumption (no external devices)4.5 W
Fuse250 V, 3.15 A, 5 × 20 mm