MBtekUNI 60 Docs
4 · TIS Tronic 260U

Control panel

Every button, indicator and main screen on the TIS Tronic 260U — START, STOP, UP, DOWN and F, plus the alarm, pump and fan indicators.

Updated

Six buttons and four indicators run the whole controller: hold F for three seconds to enter the menu, press F briefly to cycle between main screens. Everything else follows from those two gestures.

Annotated TIS Tronic 260U control panel identifying the alarm, CH pump, HUW pump and fan indicators, the stop mode indicator, the F screen-switching and menu button, the STOP button, UP and DOWN buttons, the device operating indicator and the START button
Panel view and character designation. Source: TIS Tronic 260U manual §3.1.

Indicators

IndicatorMeaning
Warning / alarmA malfunction — overheating, or a damaged temperature sensor (short circuit or breakage). Pulses red
CH pumpThe central heating pump is running
HUW pumpThe hot water pump is running
FanThe fan is in operation. Glows until the set temperature is reached, and during purge operation
STARTFlashing — ignition in progress. Constant — automatic operation mode
STOPThe device is stopped. Yellow, constantly illuminated when inactive

Buttons

Reading a screen

Annotated controller display identifying the main screen name, current parameter value, maximum parameter value, value range bar, minimum parameter value and set parameter value
Display view and description. Every main screen uses the same six elements. Source: TIS Tronic 260U manual §3.2.
ElementWhat it shows
Main screen nameWhich reading you are looking at — boiler, exhaust gas or HUW
Current parameter valueThe large figure: the live measurement
Set parameter valueThe smaller orange figure: the target
Maximum parameter valueTop of the bar — the upper end of the adjustable range
Minimum parameter valueBottom of the bar — the lower end of the adjustable range
Value rangeThe bar itself, filled to the current reading

Main screens

Press F briefly to rotate through the main screens.

Three controller main screens arranged in a cycle — hot water temperature, exhaust gas temperature and boiler temperature — with the F button at the centre
Figure 1 — the main screens. Press F to move between boiler temperature, exhaust gas temperature and hot water temperature. Source: TIS Tronic 260U manual §4.1.

Boiler temperature screen

Boiler temperature main screen showing the current reading in large type, the set value beneath it in orange, and a vertical bar with the maximum and minimum limits
Figure 2. Large figure = current boiler temperature. Orange figure below = setpoint, changed with UP and DOWN. The values above and below the ruler are the range within which the setpoint can be changed. Source: TIS Tronic 260U manual §4.1.

Exhaust gas temperature screen

Exhaust gas temperature screen showing the current reading and a bar with a padlock symbol indicating the setpoint cannot be changed
Figure 3. A padlock on the bar means the set temperature cannot be changed — for example because STANDARD mode is active. Source: TIS Tronic 260U manual §4.1.

Inactive screens

Greyed-out hot water main screen indicating the module is disabled
Figure 4. Greyed-out screens mean the module is not configured and is currently disabled. Enable it in the relevant menu — for the screen shown, the HUW menu. Source: TIS Tronic 260U manual §4.1.

Changing the setpoint takes no menu

On the boiler temperature main screen, UP and DOWN change the boiler setpoint directly. The same is true of the hot water setpoint on the HUW main screen.

NextFirst start

Powering up for the first time and working through the initial setup.

On this page