User menu

The five fan parameters in the TIS Tronic 260U user menu — maximum and minimum fan output, supervision capacity, purge time and the pause between blowups.

Updated

The user menu holds the five settings you are most likely to adjust after commissioning, and all five control the fan. Hold F for 3 seconds, then open the user menu.

The number of parameters shown depends on the controller configuration — in Brager Expert modes some of these are taken over by the algorithm.

Parameters

How supervision works

Supervision is the boiler idling on a live fire. Once the water reaches setpoint:

The fan stops driving the fire.

Every pause between blowups (5 min), the fan runs for the purge time (10 s) at the supervision capacity (35 %).

That short pulse keeps the coals alive without adding meaningful heat.

When the water drops by the boiler hysteresis (2 °C), the controller returns to full Operation.

Tuning those three numbers against each other is most of the art of running a wood boiler well.

Other menus

MenuContentsPage
Thermostat menuRoom thermostat control functionsThermostat
HUW menuDomestic hot water pump controlHot water
Boiler settingsThe full configuration listBoiler settings
Brager ExpertAdvanced options for the Brager Expert algorithmOperating modes
Software versionCurrent installed controller software
Reset to factory settingsReturns to defaults
LanguageInterface language
NextBoiler settings

Hysteresis, temperature limits, fan type, fire-up time and quenching configuration.