Quenching and fuel shortage

How the TIS Tronic 260U detects that the fire is out — by boiler temperature or exhaust gas temperature — and what it does with the fan and the central heating pump.

Updated

The controller detects a dead fire one of two ways — falling water temperature, or falling exhaust gas temperature — and the exhaust method is considerably more responsive. Choose the method in Boiler settings → Fuel shortage detection method.

Controller menu path: Boiler Settings, Fuel shortage detecting method, with the options Boiler Sensor and Exhaust gases Sensor
Boiler Settings → Fuel shortage detecting method → Boiler Sensor / Exhaust gases Sensor. The choice only appears when a PT1000 exhaust sensor is connected. Source: TIS Tronic 260U manual §4.6.

Default behaviour without an exhaust sensor

As standard, without a connected exhaust gas temperature sensor, boiler quenching (switching off) is based on the boiler temperature. The choice of method only appears once a PT1000 is connected.

Method 1 — boiler temperature

The boiler switches to quenching mode when the water temperature falls to the boiler shutdown temperature.

ParameterRangeDefaultMBtek value
Boiler shutdown temperature30–45 °C35 °C35 °C / 95 °F

When it triggers:

  • the controller turns off the fan;
  • the START diode on the front panel turns off;
  • the STOP diode lights up.
Controller menu path: Boiler Settings, Fuel shortage CH pump OFF, with the options YES and NO
Boiler Settings → Fuel shortage CH pump OFF → YES / NO. Whether the central heating pump stops when the fire goes out. Source: TIS Tronic 260U manual §4.6.
Controller menu path: Boiler Settings, CH pump shutdown delay, range 5 to 120 minutes
Boiler Settings → CH pump shutdown delay → 5–120 min. Active only when CH pump OFF is set to YES. Source: TIS Tronic 260U manual §4.6.

Method 2 — exhaust gas temperature

The boiler switches to quenching when the exhaust gas temperature falls below a set threshold and stays there for a set time.

Controller menu path: Boiler Settings, Exhaust gas temperature fuel shortage detection threshold, range 30 to 90 degrees Celsius
Boiler Settings → Exhaust gas temperature fuel shortage detection threshold → 30–90 °C. Source: TIS Tronic 260U manual §4.6.
Controller menu path: Boiler Settings, Fuel shortage detection time parameter, range 2 to 200 minutes
Boiler Settings → Fuel shortage detection time parameter → 2–200 min. Source: TIS Tronic 260U manual §4.6.
ParameterRangeWhat it does
Exhaust gas temperature, fuel shortage detection threshold30–90 °CThe exhaust temperature below which the boiler will switch to extinguishing mode
Fuel shortage detection time2–200 minThe delay — how long the exhaust temperature must fall or stay below the threshold before the controller acts

When it triggers, the controller turns off the fan, the START diode turns off and the STOP diode lights up — the same as method 1.

Why the delay matters

Exhaust temperature dips briefly every time you open a door or the fire settles. The detection time stops those dips being mistaken for a dead fire.

Pump behaviour during quenching

Two settings decide what happens to the central heating pump when the fire goes out.

ParameterRangeEffect
Fuel shortage CH pump OFFYES / NOWhether the CH pump is switched off during extinguishing mode
CH pump shutdown delay5–120 minHow long after entering extinguishing mode the pump stops. Requires the setting above to be YES

Leave the pump running if the boiler still holds useful heat. The boiler's 40 gallons of water are worth circulating into the system rather than letting them sit.

AlarmMeaning
Lack of fuelThe quenching condition above has been met
Failed fireupThe time specified in the firing-up time function expired without the boiler temperature rising above shutdown temperature + 2 °C

See Alarms for the full list and how to clear them.